NYC BC 2008: Carbon Monoxide Alarm Requirements

908.7.1.1 Affected dwelling units. Carbon monoxide alarms or detectors shall be required within the following dwelling units:
1. Units on the same story where carbon monoxide-producing equipment or enclosed parking is located.
2. Units on the stories above and below the floor where carbon monoxide-producing equipment or enclosed parking is located.
3. Units in a building containing a carbon monoxide-producing furnace, boiler, or water heater as part of a central system.
4. Units in a building served by a carbon monoxide-producing furnace, boiler, or water heater as part of a central system that is located in an adjoining or attached building.
908.7.1.1.1 Required locations within dwelling units.
Carbon monoxide alarms or detectors shall be located within dwelling units as follows:
1. Outside of any room used for sleeping purposes, within 15 feet (4572 mm) of the entrance to such room.
2. In any room used for sleeping purposes.
3. On any story within a dwelling unit, including below-grade stories and penthouses of any area, but not including crawl spaces and uninhabitable attics.
908.7.1.1.2 Installation requirements.
Carbon monoxide alarms or detectors shall comply with the power source, interconnection, and acceptance testing requirements as required for smoke alarms in accordance with Sections 907.2.10.2 through 907.2.10.4.